Air Flow Hood is a portable test equipment instrument that indicates volumetric air flow through grills, diffusers and registers. Applications include commissioning, testing, adjusting, and balancing volumetric air flow from diffusers, grilles, and registers in HVAC systems.
- Question
- Why should I buy a SMART Air Hood®?
- Answer
- The SERIES SAH SMART Air Hood® Balancing Instrument is the most accurate and easy to operate air flow hood on the market. By using the included hood standand wireless communications to the handheld, a single operator can balance a branch in less time than traditional balancing teams. Besides being lighter thanmost traditional capture hoods, the ergonomic design makes the Series SAH easy to maneuver, with less physical stress. The rugged polypropylene base hoodfeatures patented Quad Flow Design Technology for controlling air flow and minimizing back pressure, which yields superior measurement accuracy. The Wi-Fidirect communication gives reliable communication with a distance of up to 200 yards between the hood and the handheld test instrument.
- Related
- Question
- What is Predictive Balancing?
- Answer
- The current industry method of balancing is commonly referred to as proportional balancing. Proportional balancing determines the flow between each terminaland the key. The key flow changes with each adjustment of any given terminal, so the balancing technician must estimate a flow for the terminal and adjust the keyand the terminal until the correct proportion is achieved.The SMART Air Hood® is designed to provide Predictive Balancing™, an industry first for air flow balancing. Predictive balancing guides the balancing technician onwhere to go to set the proper flow for each register allowing the system to be fully optimized. The SMART Air Hood® Balancing Instrument includes the PredictAir™Application Software which reduces the number of steps in the air flow balancing process using Predictive Balancing’s Express Balance mode. Predictive Balancingis a method of predicting the optimal flow set point for each register and the order in which they should be adjusted.
- Related
- Question
- What is Quad Flow?
- Answer
- Traditional industry cone shaped air flow hoods experience two main problems when measuring flow registers; poor accuracy of flow readings and back pressurecompensation. These factors contribute to wasted energy and poor performance. Dwyer’s patent pending, state of the art, Quad Flow Design concept is based oncontrolling the recirculating air patterns that can create back pressure effects, while mixing the flow more evenly and efficiently. This well mixed flow for velocitysampling leads to superior measurement accuracy.
- Related
- Question
- Where do I send the SMART Air Hood® to be calibrated?
- Answer
- Recalibration of the SMART Air Hood® is fast and easy. Dwyer recommends recalibrating the Hood, at a minimum, once a year to ensure maximum performance.When it is time for recalibration, simply detach, by unclipping the clamps on all four sides, the four Quad Flow Sensing Grids along with the Sensor Module. TheQuad Flow Sensing Grids and Sensor Module need to be calibrated together. For your convenience, Dwyer includes with each purchase of a SMART Air Hood® acustom return calibration package specifically designed for the four Quad Flow Sensing Grids and Sensor Module. To ensure no downtime, you can purchase a newset of four calibrated Quad Flow Sensing Grids and Sensor Module, model A-SAH-CK part number 100765-09, ready to install on the jobsite. You can return theoriginal four Quad Flow Sensing Grids and Sensor Module in the custom return package to Dwyer using our RMA process or to any authorized Dwyer calibrationservice company. Once The Quad Flow Sensing Grids and Sens
- Related
- Question
- What is the warranty?
- Answer
- The SMART Air Hood® has a 1 year warranty.
- Related
- ProHood Capture Hoods Capture hoods are used to obtain volumetric air flow measurements through diffusers, registers and grilles. Capture hoods are available in a kit with one 2 ft 2 ft (610 mm 610 mm) fabric hood, frame, and base assembly. Alternate hood.
- The AccuBalance® Air Capture Hood 8380 is a multipurpose electronic air balancing instrument primarily used for efficiently taking direct air volume readings at diffusers and grilles. It features a detachable micromanometer which can be used with optional probes for increased flexibility in multiple measurement applications.
Are you buying in volume? Are you an OEM? Are you a reseller? Be sure to contact FLW directly for your special pricing.
Description
TSI Alnor EBT731 Balometer Capture Hood. The TSI Alnor EBT731 Balometer Capture Hood is a true multifunction ventilation testing instrument, capable of measuring air volume at diffusers and grills, balancing air flow systems, and troubleshooting HVAC installations. The AccuBalance® Air Capture Hood 8380 is a multipurpose electronic air balancing instrument primarily used for efficiently taking direct air volume readings at diffusers and grilles. It features a detachable micromanometer which can be used with optional probes for increased flexibility in multiple measurement applications. The testo 420 is used for volume flow measurements (main application), Pitot tube measurements and pressure measurements for air conditioning and ventilation systems. Thanks to its interchangeable flow hoods, the testo 420 can be used for air inlets and outlets of various sizes. With the additional App (Android/iOS), the readings can be. TABMASTER AIRFLOW CAPTURE HOOD MODEL 6715 Request Quote. Receive a 10% discount and free velocity grid when you purchase a TABmaster 6715 until December 30, 2019!.This offer only applies to purchases made directly from Kanomax USA. These offers do not apply to Kanomax products purchased from third-parties.
TSI Alnor EBT731 has been granted California Energy Commission Title 24 approval.
The TSI Alnor EBT731 Balometer® Capture Hood is an electronic air balancing multipurpose instrument mainly used to take direct air volume readings at diffusers and grilles. The EBT731 features a detachable micromanometer which can be used with optional probes for increased flexibility in multiple measurement applications.
The easy-to-use EBT731 is a lightweight and ergonomically designed capture hood kit which conveniently provides multiple measurement tools in one package. The EBT731 Balometer Capture Hood provides you the capability to produce energy efficient environments while staying within guidelines and regulations for ventilation systems.
Included Items- 2 ft x 2 ft. (610 mm x 610 mm) air capture hood/frame/base
- Manometer with carrying case
- (4) AA size rechargeable NiMH batteries
- Multi-country AC adapter
- 18in. (46 cm) Pitot probe
- (2) Static Pressure probes
- 16 ft (4.8 m) Neoprene tubing
- Wheeled luggage-style carrying case
- NIST traceable calibration certification
- Downloading software
- USB interface cable
- Manual
Product Specifications
Velocity RangePitot probes: | 25 to 15,500 ft./min (0.125 to 78 m/s) |
Air flow probe: | 25 to 5,000 ft./min (0.125 to 25 m/s) |
Velocity matrix: | 25 to 2,500 ft./min (0.125 to 12.5 m/s) |
Accuracy: | ±3% of reading ±7ft./min (±0.04 m/s) at velocities >50 ft./min (>0.25 m/s) |
Units: | ft./min, m/s |
Resolution: | 1 ft./min (0.01 m/s) |
PressureDifferential pressure: | ±15 in. H20 (±3735 Pa); 150 in. H20 (37.5 kPa), maximum safe operating pressure |
Absolute pressure: | 15 to 40 in Hg (356 to 1016 mm Hg) |
Accuracy: | ±2% of reading ±0.0001 in. H20 (±0.025 Pa) static and differential; ±2% of reading absolute |
Units: | in. H20, in. Hg, Pa, hPa, kPa, mm Hg, cm Hg, mm H20, cm H20 |
Resolution: | 0.00001 in. H20 (0.001 Pa) static and differential; 0.01 in. Hg (1 mm Hg) absolute |
VolumeRange: | 25 to 2,500 ft.³/min (42 to 4250 m³/h) capture hood, supply and return |
Accuracy: | ±3% of reading ±7 ft.³/min (± m³/h) at flows >50ft.³/m (>80 m³/h) |
Units: | 1 ft.³/min, m³/h, m³/min, l/s |
Resolution: | 1 ft.³/min (1 m³/h) |
RHRange: | 5 to 95% RH (temperature/RH probe) |
Accuracy: | ±3% RH |
Resolution: | 0.1% RH |
TemperatureAir Flow Capture Hood User Manual Free
Sensor in base: | 40 to 140°F (4.4 to 60°C) |
Temperature/RH probe: | 14 to 140°F (-10 to 60°C) |
Accuracy: | ±0.5°F (±0.3°) |
Units: | °F, °C |
Resolution: | 0.1°F (0.1°C) |
Literature & Docs
Videos
Videos
Digital Air Flow Capture Hood
Accessories
Air Flow Capture Hood User Manual Online
Alnor Hood and Frame Kit 28 in x 50 in 801212$535.00 $481.50
TSI 3/8 in. (9.5 mm) Diameter Duct plug, 5000 pieces, 634650003$340.00 $306.00
Alnor Hood and Frame Kit 5.25 in x 48 in 801210$425.00 $382.50
Alnor Hood and Frame Kit 28 in x 28 in 801211$425.00 $382.50
Alnor Telescoping Pitot Probe 8 in - 38 in 634634004$315.00 $283.50
Alnor Hood and Frame Kit 2 ft x 2 ft 801097$355.00 $319.50
Alnor Hood and Frame Kit 1 ft x 4 ft 801200$355.00 $319.50
Alnor Hood and Frame Kit 2 ft x 4 ft 801201$355.00 $319.50
Alnor Hood and Frame Kit 1 ft x 5 ft 801202$355.00 $319.50
Alnor Hood and Frame Kit 3 ft x 3 ft 801203$355.00 $319.50
Alnor Hood and Frame Kit 16 in x 16 in 801209$310.00 $279.00